Plug-in solar 800 watt 2026: what the inverter cuts off

With 2,000 Wp of panels facing south, an 800-watt balcony system delivers 1,616 kWh a year, while the inverter clips 497 kWh at midday peaks. Mounted upright it clips only 204 kWh.

Checked by Radif Partners · Editorial policy · How we calculate

What the 800 VA inverter clips with more panels

Clipped per year

497 kWh

Output before the inverter2,113 kWh
Share clipped23.5 %
usable after the inverter1,616 kWh
of which used at home (2,500 kWh)722 kWh
Add a battery →

The 800 watts of a German balcony power plant (Balkonkraftwerk) are a limit on the inverter, not on the panels. Section 8(5a) EEG allows a plug-in solar device 800 VA of inverter output and 2,000 Wp of installed panel output, each counted for all devices behind one point of supply together. If you connect more panel area than the inverter may deliver, you lose the peak on sunny middays: the inverter clips (Abregelung). On the German average at a 35° south tilt that is 64 kWh a year with 1,200 Wp (5 % of output), 250 kWh with 1,600 Wp and 497 kWh or 24 % with 2,000 Wp. Still, the usable amount rises from 845 kWh at 800 Wp to 1,616 kWh at 2,000 Wp, because every panel counts in the morning, the evening and in winter. Upright on a railing, or facing east or west, clipping is much smaller. The old practical limit of 600 watts no longer applies since the Solar Package I of May 2024.

Watts, watt peak, volt-amperes: three numbers on the box

A kit often says “800 watts” and next to it “2,000 Wp”. The first number describes the inverter (Wechselrichter), which turns the panels' direct current into alternating current for the socket. The law states it in volt-amperes: section 8(5a) EEG allows 800 VA. For an inverter delivering almost pure active power, 800 VA is in practice 800 watts. The second number, watt peak, is the panels' output under laboratory light of 1,000 W/m² at 25 °C. A balcony almost never sees that: most of the time a panel delivers less than its rating, which is why you may connect more panel capacity than the inverter passes on.

Before the Solar Package I (Solarpaket I), the EEG set no output limit of its own for plug-in devices; according to the Federal Network Agency, their inverters were usually rated up to 600 watts, and simplified connection depended on the technical requirements of the VDE. Since 16 May 2024 (Federal Law Gazette 2024 I no. 151) the limits are in the statute itself, together with the rule that the grid operator may not demand an extra notice. Registration is explained under register plug-in solar.

How much the inverter clips

When the panels deliver more power than the inverter may output, it holds its output at 800 VA. The surplus power is never generated; it is lost. This site's engine works it out from the distribution of sunlight over the quarter-hours of a year according to PVGIS.

German average, south, 35° tilt, 800 VA, consumption 2,500 kWh a year.
Panel outputbefore the inverterclippedusableused at home
800 Wp845 kWh1 kWh845 kWh499 kWh
1,200 Wp1,268 kWh64 kWh1,204 kWh601 kWh
1,600 Wp1,691 kWh250 kWh1,441 kWh670 kWh
2,000 Wp2,113 kWh497 kWh1,616 kWh722 kWh

Between 800 Wp and 2,000 Wp the panel area grows two and a half times, usable output by only 772 kWh. Clipping only becomes noticeable above roughly 1,000 Wp and then eats an ever larger share of each extra panel. The mini calculator above shows the value for your panel output and direction.

Why upright panels rarely reach 800 VA

On a balcony railing, panels usually hang upright. The high summer sun at midday then strikes them at a shallow angle, and output mostly stays below the limit. With 2,000 Wp upright facing south, the inverter clips only 204 kWh a year (13.9 %), leaving 1,256 kWh usable, more than twice as much as 800 Wp upright (584 kWh). Facing east at a 35° tilt, clipping is 241 kWh, facing west 283 kWh, because generation spreads over the morning or afternoon. This is where full panel capacity makes most sense. More on direction and tilt in the guide on orientation.

A battery on the panel side catches the peak

A battery that takes the direct current before the inverter charges exactly when the panels exceed 800 VA and releases the energy in the evening. With 2,000 Wp facing south and 2 kWh of capacity, clipping in the model falls from 497 to 366 kWh, and power used at home rises from 722 to 1,193 kWh. Whether it pays is worked out under plug-in solar with battery. The wording of the law matters here: the 800 VA apply to total inverter output. By that wording, a battery with its own inverter on the household circuit counts towards it.

How many panels make sense for your balcony

The question is not whether 2,000 Wp is allowed but what the last panel still adds. In money: going from 1,600 to 2,000 Wp at 35° south and 36.2 ct/kWh saves only €19 a year, because the extra power arrives mostly at midday, when surplus already flows to the grid. Upright facing south, the same step brings €18 a year. An extra panel therefore only pays for itself after its price divided by that amount, and it needs space, a safe mounting and an inverter with enough inputs.

If you can spread panels over two sides, for example two balcony faces east and west, connect them to separate inverter inputs. They then deliver at different times of day, and the 800 VA limit is reached less often than with the same area facing south. On a south wall with a gently tilted frame, by contrast, a panel output just above 1,000 Wp is often enough to use almost all of the inverter's capacity.

What does not apply to 800 watt devices

For rooftop systems without a smart meter, section 9 EEG has capped feed-in at 60 % of rated output since 25 February 2025; plug-in solar is exempt. The duty to make feed-in remotely controllable does not apply either. The only limit that holds your yield down is your own inverter. The Federal Network Agency answers output questions in its questions and answers on plug-in solar; the irradiation data come from PVGIS.

Questions readers ask

Can I connect 2,000 Wp of panels to an 800 VA inverter in Germany?

Yes. Section 8(5a) EEG sets two separate limits: 2,000 Wp of installed output and 800 VA of inverter output. Both apply to all plug-in devices behind your point of supply together. A kit with 2,000 Wp and an 800 VA inverter is therefore a lawful plug-in device. The inverter's inputs must be rated for that panel output; the data sheet says so.

How much power is clipped with 2,000 Wp facing south?

On the German average at a 35° tilt the panels produce 2,113 kWh and the inverter passes 1,616 kWh. 497 kWh, or 24 %, are lost on bright middays. With a 2 kWh battery on the panel side the loss drops to 366 kWh, because the peak flows into the battery.

Are panels between 1,600 and 2,000 Wp still worth adding?

Less than the first ones. Going from 1,600 to 2,000 Wp at 35° south raises usable output by only 175 kWh, because the peaks are already clipped. A household using 2,500 kWh consumes part of it, the rest goes to the grid unpaid. Upright or facing east, the extra panels pay off better, because more light stays below the 800 VA limit.

Do I have to upgrade my old 600 watt kit to 800 VA?

No. A device with a 600 W inverter remains lawful; 800 VA is a ceiling. Some inverters can be set higher by app or firmware if the manufacturer releases this for the model. In that case also update the inverter output in the Market Master Data Register. It only adds yield if your panels actually deliver more than 600 W at midday.

Does the 60 per cent feed-in cap apply to an 800 watt balcony kit?

No. The cap on feed-in at 60 % of rated output for new systems without a smart meter expressly excludes plug-in solar. The duty to make a system remotely controllable (section 9(1) EEG) does not apply to devices up to 2,000 Wp and 800 VA either. In your case only the inverter itself limits output.

Do two balcony kits on one flat count together?

Yes. The law speaks of a total of 2,000 Wp and a total of 800 VA behind the same point of supply. Two devices of 600 VA each add up to 1,200 VA and are over the limit. If you want a second kit on the same meter, you need either one shared inverter of at most 800 VA or an electrician and a grid application.